cvedb.io
CVE-2018-16563
MEDIUM · CVSS 5.9
EPSS exploitation probability: 0%
Published 2019-03-21T16:00:22.420 · Last modified 2026-06-17T01:44:29.750

Summary

A vulnerability has been identified in Firmware variant IEC 61850 for EN100 Ethernet module (All versions < V4.35), Firmware variant MODBUS TCP for EN100 Ethernet module (All versions), Firmware variant DNP3 TCP for EN100 Ethernet module (All versions), Firmware variant IEC104 for EN100 Ethernet module (All versions), Firmware variant Profinet IO for EN100 Ethernet module (All versions), SIPROTEC 5 relays with CPU variants CP300 and CP100 and the respective Ethernet communication modules (All versions < V7.82), SIPROTEC 5 relays with CPU variants CP200 and the respective Ethernet communication modules (All versions < V7.58). Specially crafted packets to port 102/tcp could cause a denial-of-service condition in the affected products. A manual restart is required to recover the EN100 module

Affected products

siemens — siprotec_5_with_cpu_variant_cp100

Does this affect you?

Add your gear to cvedb and we'll alert you only when siemens ships something exploited.

Check my exposure →

References