CVE detail

CVE-2019-13549 — CVE-2019-13549

Published 2019-10-25 · Modified 2026-06-17 · Vendor carel · Product pcoweb_firmware · Source nvd
HIGH
severity
CVSS-derived band
7.5
CVSS v3
0–10 scale
0.0103
EPSS probability
exploitation probability, 30d
61.0%
EPSS percentile
percentile vs all CVEs
NOT LISTED
CISA KEV
known exploited catalog

Description

Rittal Chiller SK 3232-Series web interface as built upon Carel pCOWeb firmware A1.5.3 – B1.2.4. The authentication mechanism on affected systems does not provide a sufficient level of protection against unauthorized configuration changes. Primary operations, namely turning the cooling unit on and off and setting the temperature set point, can be modified without authentication.

Remediation

No vendor-published fix data in our corpus for this CVE. Check the references below or the vendor's PSIRT / security advisories page.

References

cvedb.io · NVD · CISA KEV · FIRST EPSS · vendor advisories (CVE Program List v5). Informational only, no warranty — verify every remediation against the vendor advisory before acting on it. This product uses data from the NVD API but is not endorsed or certified by the NVD, CISA, FIRST.org or any vendor named. CVE® is a registered trademark of The MITRE Corporation.