CVE detail

CVE-2021-27196 — CVE-2021-27196

Published 2021-06-14 · Modified 2026-06-17 · Vendor hitachienergy · Product relion_670_firmware · Source nvd
HIGH
severity
CVSS-derived band
7.5
CVSS v3
0–10 scale
0.0158
EPSS probability
exploitation probability, 30d
73.0%
EPSS percentile
percentile vs all CVEs
NOT LISTED
CISA KEV
known exploited catalog

Description

Improper Input Validation vulnerability in Hitachi ABB Power Grids Relion 670 Series, Relion 670/650 Series, Relion 670/650/SAM600-IO, Relion 650, REB500, RTU500 Series, FOX615 (TEGO1), MSM, GMS600, PWC600 allows an attacker with access to the IEC 61850 network with knowledge of how to reproduce the attack, as well as the IP addresses of the different IEC 61850 access points (of IEDs/products), to force the device to reboot, which renders the device inoperable for approximately 60 seconds. This vulnerability affects only products with IEC 61850 interfaces. This issue affects: Hitachi ABB Power Grids Relion 670 Series 1.1; 1.2.3 versions prior to 1.2.3.20; 2.0 versions prior to 2.0.0.13; 2.1; 2.2.2 versions prior to 2.2.2.3; 2.2.3 versions prior to 2.2.3.2. Hitachi ABB Power Grids Relion 67

Remediation

No vendor-published fix data in our corpus for this CVE. Check the references below or the vendor's PSIRT / security advisories page.

References

cvedb.io · NVD · CISA KEV · FIRST EPSS · vendor advisories (CVE Program List v5). Informational only, no warranty — verify every remediation against the vendor advisory before acting on it. This product uses data from the NVD API but is not endorsed or certified by the NVD, CISA, FIRST.org or any vendor named. CVE® is a registered trademark of The MITRE Corporation.