CVE detail

CVE-2022-2502 — CVE-2022-2502

Published 2023-07-26 · Modified 2026-06-17 · Vendor hitachienergy · Product rtu500_firmware · Source nvd
HIGH
severity
CVSS-derived band
7.5
CVSS v3
0–10 scale
0.0065
EPSS probability
exploitation probability, 30d
48.0%
EPSS percentile
percentile vs all CVEs
NOT LISTED
CISA KEV
known exploited catalog

Description

A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature ‘Advanced security’ which must be ordered separately. If these preconditions are fulfilled, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a missing input data validation which eventually if exploited causes an internal buffer to overflow in the HCI IEC 60870-5-104 function.

Remediation

No vendor-published fix data in our corpus for this CVE. Check the references below or the vendor's PSIRT / security advisories page.

References

cvedb.io · NVD · CISA KEV · FIRST EPSS · vendor advisories (CVE Program List v5). Informational only, no warranty — verify every remediation against the vendor advisory before acting on it. This product uses data from the NVD API but is not endorsed or certified by the NVD, CISA, FIRST.org or any vendor named. CVE® is a registered trademark of The MITRE Corporation.