CENTUM series provided by Yokogawa Electric Corporation are vulnerable to cleartext storage of sensitive information. If an attacker who can login or access the computer where the affected product is installed tampers the password file stored in the computer, the user privilege which CENTUM managed may be escalated. As a result, the control system may be operated with the escalated user privilege. To exploit this vulnerability, the following prerequisites must be met: (1)An attacker has obtained user credentials where the affected product is installed, (2)CENTUM Authentication Mode is used for user authentication when CENTUM VP is used. The affected products and versions are as follows: CENTUM CS 1000, CENTUM CS 3000 (Including CENTUM CS 3000 Entry Class) R2.01.00 to R3.09.50, CENTUM VP (I