A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted series of network requests can lead to a denial of service. An attacker can send a sequence of unauthenticated packets to trigger this vulnerability.An attacker can trigger this denial-of-service condition by sending a single Modbus TCP message to port 502 using the Write Single Register function code (6) to write the value 1 to register 4352. This action changes the Modbus address to 15. After this message is sent, the device will be in a denial-of-service state.
Add your gear to cvedb and we'll alert you only when socomec ships something exploited.
Check my exposure →This product uses data from the NVD API but is not endorsed or certified by the NVD. Informational only; not professional security advice.